facebook Google+ twitter flickr youtube in crestron
Produktkategorien
Produkt
Produktfoto

DIN-AO8

8-Kanal analog Ausgangsmodul

8 Kanal analog Ausgangsmodul 0 -10 Volt DC Ausgänge 20mA pro Kanal. 1024 Schritte (10 bit). Zur Ansteuerung von z.B. Heizungsstellantrieb, externen Dimmern… Cresnet Anschluss, frontseitige Handbedienung und Anzeige der Cresnet ID, Override Eingang. Format 6 TE.

The DIN-AO8 is a DIN rail-mounted automation control module that provides eight analog output ports for interfacing with third-party lighting and heating/cooling systems.

Analog Outputs
Each analog output port provides a 0 to 10 Volt DC control signal ideally suited for controlling 0-10V lighting dimmers and heating/cooling valves. Ten-bit resolution ensures precise recall of lighting and climate control settings and smooth ramping between levels.

Override Input
An override input is provided to allow an external contact closure to momentarily override the control system program and set each output to its override preset level. Levels can be adjusted and saved locally from the front panel, or remotely via software.

DIN Rail Installation
The DIN-AO8 is designed to snap onto a standard DIN rail for installation in a wall mount enclosure or mounted on a wall panel. Wiring connections are made using detachable screw terminals positioned along the top and bottom, clearly accessible from the front for easy installation and servicing. All setup controls and indicators are positioned on the center front panel. When installed in an enclosure utilizing 45 mm cutouts, the DIN-AO8's front panel stays accessible while the connections are concealed.

Cresnet®
The DIN-AO8 communicates with a DIN-AP2 2-Series Automation Processor, or other Crestron 2-Series control system, via the Cresnet control network. Cresnet also powers the DIN-AO8. A pair of Cresnet ports is provided on the DIN-AO8 allowing for easy daisy-chaining of several DIN Rail Series automation control modules.

Key Features

 

  • Eight 0-10V analog output control ports
  • Interface for 3rd-party lighting and heating/cooling
  • Fully programmable functionality via DIN-AP2
  • Setup via front panel or software
  • Override input
  • Cresnet communications
  • 6M wide DIN rail mounting

Connections
  OUTPUTS 1 – 8 (4) 4-pin 3.5mm detachable terminal blocks comprising (8) analog output ports;
Voltage Control Range: 0 to 10 Volts DC;
Maximum Sink/Source Current: ±20mA per channel;
Output Resolution: 1024 levels (10 bit)
  NET (2) 4-pin 3.5mm detachable terminal blocks, paralleled;
Cresnet slave port
  OVERRIDE (2) 2-pin 3.5mm detachable terminal blocks, paralleled;
Sensing input for external low-voltage contact closure;
Activates override mode when a closure is present;
Minimum Closure Rating: 10mA (per module) at 24 Volts
Controls & Indicators
  OUTPUTS 1 – 8 (8) Red LEDs and (8) miniature pushbuttons for status indication and local control of each channel
  NET ID (2) 7-Segment green LED digits and (2) miniature pushbuttons for setting Cresnet ID; digits also display output levels
  SETUP (1) Red LED and (1) recessed miniature pushbutton for enabling setup mode and touch-settable ID
  OVR (1) Red LED and (1) miniature pushbutton for enabling override mode and saving override presets
  PWR (1) Green LED, illuminates when DC power is applied to the NET port
  NET (1) Yellow LED, indicates communication with the control processor
  RESET (1) Recessed miniature pushbutton, resets internal processor
Enclosure
  Light gray polycarbonate housing with polycarbonate label overlay, UL94 V-0 rated, 35mm DIN EN 60715 rail mount, DIN 43880 form factor for enclosures with 45mm front panel cutout, occupies 6 DIN module spaces (108mm)
Power Requirements
  Cresnet Power Usage 6 Watts (0.25 Amps @ 24 Volts DC)
Environmental
  Temperature 32° to 104°F (0° to 40°C)
  Humidity 10% to 90% RH (non-condensing)
  Heat Dissipation 21 BTU/hr
Dimensions
  Height 3.71 in (9.42 cm)
  Width 4.18 in (10.60 cm)
  Depth 2.35 in (5.95 cm)
Weight
  6.3 oz (179 g)

Typical DIN-AO8 Application
Models Included: DIN-AO8

Shows typical connections to and from a DIN-AO8.

Application Diagram (PDF - 688 K)
Rev. Date: 7/8/2008

Application Diagram

DIN Rail Automation System
Models Included: DIN-1DIMU4, DIN-AO8, DIN-AP2, DIN-HUB, DIN-PWS50

DIN Rail processor with lighting, HVAC, security and AV integration.

Application Diagram (PDF - 2.76 M)
Rev. Date: 10/22/2008

Application Diagram

Publications

Spec Sheet

Spec Sheet (PDF)

Installation and Operations Guide

Installation And Operations Guide (PDF - 4.5 M)
Doc. No. 6663A
Rev. Date: 5/1/2008

Engineering Specs

Engineering Specs (PDF - 293 K)
Rev. Date: 10/31/2008
Note: This document covers the DIN Rail lighting control products series.

CADs, Drawings and Revit Files

Zoomable Drawing

Zoomable Drawing

Cad Files

Cad Files (ZIP - 629 K)
Rev. Date: 4/21/2008

Available Models

Model Description      

DIN-AO8

DIN Rail Analog Output Module

 

 

 

Invitation to Tender

DIN-AO8 (TXT - 1.17 KB)
Letzte Änderung 11.11.2012