GLA-BMS

Gebäudemanagement Interface

Ethernet basiertes Gateway, welches direkte Befehle und Rückmeldungen mit folgenden Protokollen ermöglicht: BACnet/IP, BACnetMSTP (RS-485), Modbus TCP/IP, Modbus RTU (RS-485), Lonworks, Metasys N2 Open (Johnson Controls). Die Programmierung erfolgt mit der Standard Crestron Software. Stromversorgung 24 V/ AC benötigt.

The GLA-BMS is an Ethernet based "protocol translator" which allows a Crestron system to communicate directly with any number of building management protocols. Programmable like any other Crestron Ethernet device, the GLA-BMS makes it easy to interface with:

  • BACnet®/IP
  • BACnet®/MSTP (RS-485)
  • Modbus® TCP/IP
  • Modbus® RTU (RS-485)
  • LonWorks®
  • Metasys® N2 Open (Johnson Controls)

This product is available as part of a complete engineered Crestron Green Light® system. Please contact Sales Support Services for more information.

Key Features

 

  • Interfaces Crestron systems with building management systems
  • Native Crestron Ethernet communications
  • Compatible with a wide range of protocols
  • Supports BACnet, Modbus, LonWorks, and Metasys N2

Connections
Ethernet 10BaseT RJ45
Serial RJ45 (RS-232) Terminal (RS-485)
Power Requirements
24 VAC floating; 9-30 VDC @ 5W
Mounting
Desktop, Wall, DIN Rail
Environmental
Temperature 32° to 144°F (0° to 60°C)
Humidity 10% to 95% RH (non-condensing)
Dimensions
Height 2 in (5.1 cm)
Depth 3.9 in (9.9 cm)
Width 3.9 in (9.9 cm)
Standards & Certifications
UL Listed, CE Marked, FCC tested to comply with FCC part 15, ODVA Ethernet/IP Conformance Tested

GLA-BMS Connectivity Example
Models Included: GLA-BMS

Illustrates the various connections to the GLA-BMS. Shows the different systems that can be controlled by a Crestron control system through the GLA-BMS.

Application Diagram (PDF - 1.22 M)
Rev. Date: 6/28/2011

Application Diagram

Publications

Spec Sheet

Spec Sheet (PDF)

CADs, Drawings and Revit Files

Revit Files

Revit (ZIP - 618 K)
Rev. Date: 8/29/2011

Available Models

Model Description

GLA-BMS

Building Management Systems Interface; requires factory configuration, programming and start-up. Please contact Crestron Sales Support Services.

 

 

 

Invitation to Tender

GLA-BMS (TXT - 460 B)
Letzte Änderung 11.11.2012